We are reckoned in the global market as one of prominent High Voltage Insulating Sheet Manufacturers. Our High Voltage Insulating Sheet is an adhesive coated sheet that augments insulation and safeguards against accidental induced discharge. We manufacture High Voltage Insulating Sheet from premium quality non tracking cross linked polyolefin material that meets the parameters of ANSI C37.20.2.


Specifications :
  • Renders flashover protection up to 17.5 K.V.
  • Suitable for MV application up to 36KV

Salient Features :
  • Rugged construction
  • Easy installation (By hot air gun and gas torch)
  • Have corrosion resistant properties that prevent bus bar from chemical corrosion induced by salt, acid, alkali, etc.
  • UV and weather resistant properties
  • High dielectric strength
  • When treated with heat, sheet shrinks according to the shape required
  • Apt for indoor and outdoor use
  • Halogen free
  • Flame retardant

Storage :
  • Can be stored at temperature up to 50°C. Storage for indefinite time at this temperature does not cause any performance loss.

Apt to insulate :
  • Busbar Joint such as busbar tees, elbows, etc.
  • Tube and tape connections


Technical Specifications

PropertiesValueStandard
Physical
Tensile Strength10 N/mm2 (MPA)(min)ASTM D638
Ultimate Elongation300% (Min.)ASTM D638
Water absorption0.5 % (max.)ASTM D570
Hardness45 ± 10 Shore DASTM D2240
Thermal
Accelerated ageing(120oC for 500 Hrs)ASTM D2671
Tensile Strength9 N/mm2 (Mpa) (min.)ASTM D 638
Ultimate Elongation250% (Min.)ASTM D 638
Low temperature Flexibility (-40oC for 4 Hrs.)No CrackingASTM D2671
Heat Shock (250oC for 30 Min.)No Cracking or flowingESI 09-11
Shrink Temperature125oCIEC 216
Continuous Temperature limit-40oC to +105oCIEC 216
Electrical
Dielectric Strength18 KV/mm. (Min.)ASTM D149
Volume Resistivity1 x 1014 Ohm.cm(min.)ASTM D257
Dielectric Constant5 (Max.)ASTM D150
Resistant to track & erosionNo tracking,erosion or
flame failure upto 3.25
KV for 20 min.
ASTM D2303


Clearances with Insulation



VoltageMedium wall Tube (GMHS) Heavy Wall Tube (GHHS) UN-Insulated Bus bars
Ph. To Ph. Ph. to gr. Ph. to Ph. Ph. to gr.
12KV65753545120
17.5 KV 851055565160
24 KV 11515070100220
36 KV 200285140190320


Product Selection



For 'T' & 'L' Connection
Busbar Width (mm)Cut Size Needed (mm)No. of Installations (mm)
25275 x 2258
50325 x 2506
75400 x 2754
100450 x 3253
150550 x 4252

Note : The above table should be used as a guideline only. Please try with one or two joints before adopting final cut size.The busbars are assumed to be insulated to 25mm. from the joint. Cut size should extend minimum of 100mm. on each leg of the joint before shrinking and should overlap existing insulation by 65mm. after shrinking.

Ordering Information



GALA CODELENGTHWIDTHTHICKNESS AFTER RECOVERY
LS (mm)WS (mm)ADHESIVE (mm)TOTAL THICKNESS (mm)
GMHS120043031.54.5
GMHS120043041.55.5
VOID FILLING MASTIC30060--PIECE
SEALANT MASTIC30020--PIECE
TOOL - 1BASIC CLAMP AND BRACKET KIT)KIT
TOOL - 2(EXTENDED CLAMP AND BRACKET KIT)KIT

Note : If required, one piece of Red sealing mastic is applied on each leg of the joint and one or two pieces of Black sealing mastic is used
to cover uneven shapes.

 

INQUIRY FORM


  Contact Information * fields are mandatory  
Contact Person *  
Company Name *  
Address *  
Country *  
Email ID *  
Phone Number  
Mobile Number *  
Fax  
  Details
Subject *  
Details *  
   


Select Language:   English   French   German   Italian   Portuguese   Spanish